Test Results – SonicClear 2mm 120mm overlap attenuation

SonicClear curtain attenuation test report

Download the RMIT University laboratory test report for the Flexshield SonicClear curtain to review airborne transmission loss and Weighted Sound Reduction Index data for a 2mm clear PVC curtain configuration.

What you’ll find in the report

  • Airborne transmission loss results from 100Hz to 5000Hz
  • A Weighted Sound Reduction Index of Rw 17
  • Spectrum adaptation terms of C 0dB and Ctr -1dB
  • Test data for 2mm SonicClear panels with 270mm overlaps
  • One-third octave band transmission loss data and the Rw reference curve
  • Testing completed in accordance with AS 1191-2002
  • Rw determined in accordance with AS/NZS ISO 717.1-2004
  • Testing completed by RMIT University’s NATA-accredited Applied Acoustics Laboratory

The report documents laboratory testing of a 2mm SonicClear curtain configuration using 1370mm-wide panels with 270mm overlaps, mounted on a 500 Series Acoustic Track. The panels were installed vertically with a nominal surface density of 2.44kg/m². Attenuation 2mm Sheet SonicClea…

The tested curtain achieved Rw (C;Ctr) = 17(0;-1), with measured transmission loss results provided across frequencies from 100Hz to 5000Hz.